Electronic Ballast FAQ's
What is ballast? Ballast is an electrical device that supplies
sufficient voltage to start the flow of arc current in a fluorescent
lamp, and then regulates the proper arc current to the lamp.
Electronic Ballasts are able to operate lamps at high frequencies
because they utilize semiconductor component circuitry instead of
the standard electro-magnetic transformer circuit operating at line
frequency.
Ballast Factor is the measure of the light output (lumens)
of a ballast and lamp combination in comparison to the ANSI standard
ballast operated with the same lamp. Electronic ballasts generate
10% more lumens, per watt, verses electromagnetic ballasts, due
to the high frequency operation of the fluorescent lamps.
Rapid Start ballasts provide continuous filament voltage
which allows for a lower starting voltage. A grounded reflector
close to the lamp, and a grounded line circuit are required to provide
a capacitive starting aid for the lamp. Rapid Start used to be considered
the best for frequently switched applications.
Programmed Start ballasts improve on the rapid start concept
by delaying the starting voltage until the filament is fully heated.
This results in a 50 percent greater number of safe starts during
a normal lamp life. After the lamp is started the filament voltage
is reduced to a minimum, saving energy and enhancing longer lamp
life.
eChokeTM is the name of the new Ballast.
Instant Start ballasts start the lamps without preheating
the filaments. This requires a higher starting voltage to start
the arc current. Because there is no filament voltage applied by
the ballast it is the most energy efficient.
Do electronic ballasts run cooler? Electronic ballasts generate
less heat than electro-magnetic ballasts by using highly efficient
semi-conductor circuitry. This saves money on air conditioning costs.
Are electronic ballasts lighter? Electronic ballasts are
lighter in weight than electro-magnetic ballasts because they utilize
semi-conductor circuitry instead of a transformer based design.
Are electronic ballasts cheaper to operate? Electronic ballasts
pay for themselves over time because up to 50% less energy to create
the same amount of light as electromagnetic ballasts.
Do electronic ballasts provide flicker free light? Electronic
ballasts operate the lamps at roughly 25KHZ where electro-magnetic
ballasts operate a 50HZ. The high frequency operation prevents stroboscopic
effect, and makes the light appear continuous to the human eye with
no perceptible flicker.
Do electronic ballasts make noise? Because electronic ballasts
do not have the auto transformer that is inherent to an electro-magnetic
ballast, the characteristic "hum" of a magnetic ballast
is not present in an electronic ballast. The electronic ballast
generates a small noise, much less than a magnetic ballast of a
similar application. Other factors such as the lighting fixture
and room characteristics affect the noise level.
What is RFI? Radio Frequency Interference is any signal,
either radiated from the lamps, or conducted on the power line,
that interferes with radio or television reception. Electronic ballasts
have built in filter circuits that for RFI and EMI for eliminating
these unwanted signals, when the ballast is installed properly with
a good earth ground.
What is High Power Factor? High Power Factor ballasts correct
for the loading effect of the ballast on the supply voltage. This
results in more efficient operation. All Universal Lighting electronic
ballasts are High Power Factor ballasts.
|